Class II A2 vs B2 Biosafety Cabinets: How to Choose

November 18, 2026

Last updated November 2026 · LORDERAN buying guide

Short answer: choose a Class II Type A2 cabinet for most biological work, including cell culture and BSL-2 microbiology, when no volatile toxic chemicals are used. Choose a Type B2 only when the same work also involves volatile toxic chemicals or radionuclides and your building can supply a dedicated exhaust duct and fan.

Class II Type A270 / 30
% of air recirculated / exhausted
Duct
Not required
Exhaust goes
Into the room, or a canopy connection
Choose it for
Biological work without volatile toxic chemicals
Class II Type B20 / 100
% of air recirculated / exhausted
Duct
Hard-ducted, dedicated exhaust
Exhaust goes
Outside, through the building exhaust fan
Choose it for
Biological work with volatile toxic chemicals or radionuclides

How each cabinet moves air

Both types protect three things at once. Room air drawn in through the front grille protects the operator, filtered air flowing down over the work surface protects the sample, and the exhaust filter protects the room. The difference is where the air goes after it passes the work surface.

Class II A2

About 70% recirculates through the supply filter. About 30% leaves through the exhaust filter.

30% out to the room 70% back Supply ULPA, downflow Room air in Front grille, under the work surface Sash

In an A2, about 70% of the downflow is filtered and blown back over the work area, and about 30% is filtered and exhausted. HEPA and ULPA filters trap particles, not chemical vapors, so any vapor released in the work zone keeps circulating inside the cabinet and can return to the room.

Class II B2

Nothing recirculates. All of the air leaves through a hard duct to the building exhaust.

100% out hard duct Top intake Supply ULPA, downflow Room air in Front grille, under the work surface Sash

In a B2, nothing recirculates. The building exhaust pulls all of the air through the cabinet and out through the exhaust filter, so vapors leave with it. This also makes a B2 dependent on the building: if the exhaust fails, the cabinet becomes pressurized and air from the work zone can be pushed out of the front opening. BMBL calls for an interlock that stops the supply blower and an alarm that warns the user when exhaust flow drops.

Room air drawn inFiltered air inside the cabinetAir leaving the cabinet

A2 and B2 side by side

Class II Type A2
Class II Type B2
Air recirculated inside the cabinet
About 70%
None
Air exhausted
About 30%, through the exhaust HEPA/ULPA filter
100%, through the exhaust HEPA/ULPA filter
Minimum inflow velocity
100 fpm (0.5 m/s)
100 fpm (0.5 m/s)
Exhaust connection
Into the room, or a canopy (thimble) connection to the building exhaust. Never hard-ducted.
Hard-ducted to a dedicated building exhaust system
Volatile toxic chemicals
Not with room exhaust. Minute amounts only with a canopy connection and an exhaust alarm.
Small amounts, justified by a risk assessment
What the building must provide
A power outlet (canopy connection optional)
Exhaust duct, exhaust fan, airflow alarm and interlock, and make-up air
Conditioned room air removed
Small, and only with a canopy connection
Up to 1,200 cfm
Typical work
Cell culture, microbiology, clinical samples, molecular biology
Biological work that also uses volatile toxic chemicals or volatile radionuclides
A2

When an A2 is the right choice

  • Cell and tissue culture, microbiology and virology at BSL-1 or BSL-2
  • Clinical and diagnostic samples, PCR set-up and sterile media handling
  • Labs without a dedicated exhaust duct, or where the cabinet may be moved later

If a protocol needs minute amounts of volatile chemicals, an A2 can be connected to the building exhaust through a canopy (thimble) connection with an exhaust alarm. Unlike a hard duct, a canopy leaves an air gap between the cabinet and the duct, and BMBL states that A2 cabinets should never be connected directly to the building exhaust.

B2

When you need a B2

  • Protocols that combine biological agents with volatile toxic chemicals
  • Work with volatile radionuclides
  • Your biosafety officer's risk assessment calls for total exhaust

A B2 only works as well as the building exhaust behind it. Check the four items below with your facilities team before you order.

What a B2 needs from the building

Before ordering a B2, confirm with your facilities team that the building can provide:

  1. 1
    Exhaust fan and duct routeA dedicated exhaust fan sized for the cabinet, and a duct route to the outside.
  2. 2
    Airflow alarm and interlockAn airflow monitor and alarm, and an interlock that stops the cabinet blower if exhaust flow drops.
  3. 3
    Make-up airEnough supply air to replace what the cabinet removes: BMBL puts it at up to 1,200 cfm, and a LORDERAN B2 exhausts about 620 to 1,060 cfm depending on width.
  4. 4
    Field certificationCertification after installation and balancing.
Roof Ceiling Lab floor B2 cabinet 1 Exhaust fan 2 Alarm + interlock 3 Make-up air 4 Certify on site

Cost of ownership

A B2 costs more to run. It removes conditioned room air for as long as it operates: a 3 ft LORDERAN B2 exhausts about 1,050 m³/h (620 cfm), roughly three times the 360 m³/h that a 3 ft A2 returns to the room through its exhaust filter.

Every LORDERAN B2 ships with an exhaust blower and a 4 m PVC duct (300 mm diameter). The route through the building, the roof penetration, airflow balancing and the extra supply air are still building work outside the cabinet price. An A2 that exhausts into the room needs only a power outlet.

Both types should be field certified to NSF/ANSI 49 when installed, after they are moved, and at least once a year.

Air each cabinet sends out of its exhaust, m³/h

LORDERAN listed figures. A2 air returns to the room; B2 air leaves the building and must be replaced.

A2, 3 ftreturns to room
360 m³/h (212 cfm)
A2, 5.3 ftreturns to room
620 m³/h (365 cfm)
B2, 3 ftleaves the building
1,050 m³/h (618 cfm)
B2, 4.4 ftleaves the building
1,270 m³/h (748 cfm)
B2 Pro, 5.25 ftleaves the building
1,800 m³/h (1,059 cfm)

Bars share one scale, starting at zero.

A three-question check

QUESTION 1Will volatile toxic chemicals or volatile radionuclides be used in the cabinet?
No
Choose an A2Room exhaust, no duct needed.
Yes
QUESTION 2Are they only minute amounts, and can the A2 be canopy-connected with an exhaust alarm?
Yes
A2 with a canopy connectionMay be enough. Confirm with your biosafety officer.
No
QUESTION 3Can the building provide a dedicated exhaust duct and fan?
Yes
Choose a B2Plan the four building items above.
No
Plan the ductwork before you orderThe B2 cannot run safely without it.
Other option: Class II Type C1A C1 cabinet can run either recirculating or canopy-connected. LORDERAN does not currently offer a Type C1.
Other option: chemical fume hoodThe right tool for chemical work that needs no sample protection.
Sample protection only: laminar flow hoodA clean bench keeps particles off the sample and blows the air toward you. See laminar flow hood vs biosafety cabinet.

LORDERAN A2 and B2 cabinets

2 × ULPA 99.9995%ISO Class 3 work zoneMotorized sashAirflow + filter alarms≤ 67 dB(A)110 V or 220 V3-year warranty

Every LORDERAN Class II cabinet uses two ULPA filters rated 99.9995% at 0.12 μm, one for the downflow and one for the exhaust, which gives an ISO Class 3 work zone. All of them have a motorized, UV-blocking front window, audible and visual alarms for abnormal airflow, filter change and an unsafe window height, and interlocks that keep the UV lamp off while the window is open. Noise is 67 dB(A) or less, every model comes in 110 V or 220 V, and the warranty is 3 years.

Prices as of November 2026, with free delivery and duties paid to your loading dock.

Which model fits your lab

WidthChoose by the equipment that stays inside and how many people work at once. Interior width runs from about 910 to 940 mm (36 to 37 in) on a 3 ft cabinet to 1,700 mm (67 in) on the widest models, with 600 to 670 mm (24 to 26 in) of depth. The 2 ft benchtop has a 600 × 500 mm (24 × 20 in) interior.
CertificationIf your institution or certifier requires an NSF/ANSI 49 listed cabinet, choose the NSF certified A2. Its NA versions read airflow in fpm, most widths are tested at a 10 in (254 mm) opening, and it exhausts 35 to 40% of its air rather than 30%.
ControllerThe Pro models show live inflow and downflow velocity, temperature and humidity, filter pressure and filter life on a 7-inch touch screen. The standard controller shows filter life and lamp and fan run time, with the same alarms.
SpaceThe 2 ft benchtop A2 suits a single operator with small volumes, sits on an existing bench and is the quietest model, at 65 dB(A) or less.
Total exhaustSize the building exhaust and the room's supply air for the B2 width you choose. A 3 ft B2 moves about 1,050 m³/h and a 5.25 ft B2 Pro about 1,800 m³/h.

Questions buyers ask

Can an A2 cabinet be hard-ducted to the building exhaust?

No. An A2 should use a canopy (thimble) connection with an exhaust alarm. BMBL states that Type A1 and A2 cabinets should never be connected directly to the building exhaust system.

Is a B2 safer than an A2?

Not for biological work alone. Both types meet the same 100 fpm minimum inflow and protect the operator, the sample and the room. A B2 adds removal of chemical vapors, but it depends on the building exhaust, and an exhaust failure pressurizes the cabinet.

Can a biosafety cabinet replace a chemical fume hood?

No. A fume hood protects the operator from chemical vapors but does not protect the sample or filter what it exhausts. A recirculating A2 filters particles but not vapors. Use a B2, or an A2 with a canopy connection for minute amounts, only when biological and chemical hazards are combined.

What inflow velocity do LORDERAN cabinets run at?

The standard and Pro A2 and B2 models run at 0.53 m/s (about 104 fpm) inflow and 0.33 m/s (about 65 fpm) downflow, both held within ±0.025 m/s and tested with the front window at 200 mm (8 in). That is above the 100 fpm minimum inflow for Class II Type A2 and B2 cabinets.

How often does a biosafety cabinet need certification?

Field certification to NSF/ANSI 49 is done when the cabinet is installed, after it is moved, and at least once a year.