How to Use a Rapid Temperature Change Chamber: Load, Program and Maintain

November 21, 2026

Last updated November 2026 · LORDERAN how-to guide

Short answer: a rapid temperature change chamber ramps between −70 and +150 °C at a rated average of 5, 10 or 15 °C per minute, measured with an empty chamber. Your load slows it, so fill no more than three quarters of the volume, stagger the samples in the airflow and use open fixtures. Program each ramp as temperature span divided by rate, set the dwell long enough for the product to reach temperature, and loop the cycle. Keep the door closed mid-ramp, dry the chamber after sub-zero tests and look after the humidifier water. Figures come from the LORDERAN rapid temperature change chamber user manual.

1. What the rated rate means

Cooling comes from a two-stage cascade refrigeration circuit and heating from ceramic elements under PID control. The rated rate is a non-linear average at no load, commonly taken between 10 % and 90 % of the span. The chamber is fastest mid-range and slower near −70 °C and +150 °C.

Average, not linear

The first and last few degrees are slower.

90 %10 %+150 °C−70 °Ctime →Rated rate = average, empty chamber

Load in the airstream

Every kilogram inside must heat and cool too.

air out, topreturn, bottomStagger, space, 3/4 full at most
Air temperatureAirflow and 10 to 90 % bandSamples

2. Install it

Electrical connection is for a qualified electrician; refrigerant pipes are for certified technicians only.

  1. 1
    Unload levelKeep it horizontal, lift from the long side with the forks spread and never use steel cables on a crane.
  2. 2
    SiteLevel, stable floor; ambient 5 to 32 °C at up to 85 %RH; low dust, nothing flammable and no fire detector directly above. Level the four casters with a spirit level.
  3. 3
    Room for airKeep the 40, 60 and 80 cm clearances from the manual. Air-cooled units slow noticeably when the room rises above about 30 °C, so size the room ventilation to the rated power.
  4. 4
    Power380 or 480 V three-phase to the nameplate, ±10 %, earth resistance up to 4 Ω, on a dedicated lockable breaker. With the phases in the wrong order the chamber will not start.
  5. 5
    Water and drainWater-cooled units: 5 to 32 °C water with shut-off valves and a Y-strainer, supply to IN, return to OUT. Keep the drain end out of the water: it also equalizes pressure during fast ramps.

3. Load for fast ramps

Air leaves at the top of the workspace and returns at the bottom, so every sample should sit in that stream. Remove the cable ties from the sample racks before the first run; they melt at high temperature.

  1. 1
    Three quarters at mostKeep the total load volume below 3/4 of the working volume.
  2. 2
    Stagger and spaceLeave at least one sample thickness clear on every side. Nothing on the bottom shelf or in front of the rear outlet.
  3. 3
    Open fixturesLight, perforated fixtures; spread the mass so one dense block does not shield the rest.
  4. 4
    Leads and powerRoute leads through the test port and seal it when unused. Tell LORDERAN the power any powered samples dissipate: it uses up cooling capacity.
  5. ✕
    Never insideExplosive, combustible, corrosive or conductive dispersible samples. Batteries and energized samples need a risk assessment and an interlock through the test-sample terminal.

4. Program a cycle

Ramp time in minutes is the span divided by the rate, rounded up and entered as hours.minutes in TIME. The manual's example runs −40 to +125 °C at 10 °C/min for 100 cycles: 165 ÷ 10 = 16.5, so each ramp is 0.17.

  1. 1
    Segments 001 to 005Ramp to +125 °C, hold 15 min, cool to −40 °C in 17 min, hold 15 min, heat back in 17 min. Add a last segment to +25 °C so the door can be opened safely.
  2. 2
    Loop and waitLOOP SET begin 02, end 05, cycle 100. WAIT ON with a 2 °C zone, so the dwell only starts once the chamber is there.
  3. 3
    Before you runPreview with CURVE. Set the over-temperature protector from the profile's highest temperature, and a logging interval shorter than the 60 s default.
  4. 4
    New productsPut a thermocouple on the product through the test port and run two or three cycles to measure how far it lags the air.
125−40001002003004005002003loop 02–05 × 100

5. Run, humidity and shutdown

Start with the breaker, POWER, then RUN and START. Stop with STOP, then POWER, then the breaker. Never cut main power during a run.

While it runs

  1. 1
    Door shut mid-rampHold or stop the program and let it approach room temperature first.
  2. 2
    Read PV firstCheck the chamber temperature on screen just before opening; it can swing faster than you expect.
  3. 3
    GlovesAbove 55 °C or below 0 °C, heat- or cold-resistant gloves.

Humidity tests

  1. 1
    WaterDeionized, RO or distilled, up to 5 µS/cm. Never tap, softened or treated water.
  2. 2
    TankBetween 1/2 and 3/4 full, checked before each humidity test.
  3. 3
    HUMI OFFIn segments below 0 °C or above 100 °C and the ramps leading to them.

After sub-zero tests

  1. 1
    Dry itRun 60 °C with HUMI OFF for 30 minutes to clear frost before a cold phase and before shutdown.
  2. 2
    Power cut settingHot Start resumes the segment, but the first cycle after recovery does not count.
  3. 3
    Long idleDrain and dry the water system before two weeks or more of shutdown.

Do not touch surfaces above 38 °C or below 0 °C. The condenser fan can start at any time while the chamber has power, and the circulation fan keeps running about 5 minutes after a stop.

Alarms

DI1, DI2 and short-circuit alarms power the chamber off; let it cool and follow the manual before restarting. For the others, fix the cause and tap Reset.

ALARMMEANINGWHAT TO DO
DI3 Dry-fireThe humidifier ran without enough water.Fix the water supply, then tap Reset.
DI4 / DI5 Compressor overloadSecond- or first-stage compressor overload.The chamber cannot start. Check ventilation, voltage and the condenser; call service if it repeats.
DI6 Phase sequencePhases connected in the wrong order.An electrician swaps any two phase conductors with the power off.
DI7 First-stage pressureFan or cooling water fault, dirty fins, hot room.Check the fan or water flow, clean the condenser fins, check the room temperature.
DI8 Low waterThe humidifier tank is low.Top up, then tap Reset once the background turns green.
DI10 Circulation fanThe circulation fan stopped.Fix the cause, then tap Reset.

Maintenance

Most routine work is on the humidifier water system. Never run the pump dry, and never let water freeze in the humidifier, pump or pipes.

BEFORE HUMIDITY TESTSWater checkLevel between 1/2 and 3/4, clear water, empty tray, wet-bulb gauze in place.
WEEKLY AND MONTHLYHoses and waterWeekly: check hose joints and empty the tray. Monthly: replace the water and clean the pump and return filters.
EVERY 3 MONTHSGauze and alarmReplace the wet-bulb gauze, inspect the level switch and test the low-water alarm.
6 TO 12 MONTHSServiceHave the humidifier checked for scale and replace aged hoses. Keep condenser fins and door seals clean.
User manualRapid temperature change chamber
Buying guideEnvironmental test chambers
How-to guideThermal shock chambers
Product100 to 1000 L, 5 to 15 °C/min

Questions

Will my test reach 15 °C/min?

The rated rate is an average at no load. Samples, fixtures and shelves all add mass to heat and cool, so a loaded chamber ramps more slowly, especially near the ends of the range.

How long should the dwell be?

Long enough for the product, not just the air, to reach temperature. Measure the product lag with a thermocouple over two or three cycles.

What water does the humidifier need?

Deionized, RO or distilled water up to 5 µS/cm. Replace it monthly and the wet-bulb gauze every three months.

Which units need cooling water?

The faster and larger versions: for example the 250 L at 15 °C/min, the 500 L at 10 and 15 °C/min and every 1000 L version. Your nameplate shows AIR or WATER.